Core Interconnection & Connectivity

Strategically located in a core interconnection site, 325 Hudson has a robust infrastructure with direct access to 21 major multichannel video service providers, six transatlantic cables, and three peering exchanges, including NYIIX and DE-CIX, as well as cloud on-ramps to Microsoft Azure ExpressRoute and AWS Direct Connect. With flexibility and options for expansion, our responsive operational team will keep you connected with more space, power, and connectivity as you grow.

Integration Model 8-6-18-min.jpg

CONNECTIVITY

  • Premier core interconnection site in New York City
  • Carrier neutral, building owned and managed Meet Me Room
  • No monthly recurring charges for cross connects
  • Network operators: 35+
  • Points of entry ("POE"): 2 diverse POEs
  • Risers: pre-built innerduct system from ECS to POEs to Meet Me Room
  • Colocation: cabinets and cages available

COOLING

9th Floor

  • Cooling system capacity: 160 tons (N+1), backed up by generators
  • Production floor cooling: CRAC Units and in-row cooling units (N+1) with cold aisle containment
  • Glycol condenser water distribution: closed-loop system (N+1), additional capacity for expansion

8th Floor

  • Glycol condenser water distribution: closed-loop system (N+1), additional capacity for expansion
  • Cooling system capacity: 80 tons (N+1), backed up by generators
  • Production floor cooling: CRAC units (N+1) with cold/hot aisle deployment

INFRASTRUCTURE

  • Ceiling heights (slab to slab): 13'
  • Column spacing: 18' and 21'
  • Floor loading: 150 lbs/sf
  • Loading dock: secure dock
  • Freight elevators: 8,000 lbs capacity
  • Fire suppression: pre-action, dual interlock, dry pipe
  • Cable management: overhead ladder rack
  • Outside the 100-year floodplain
  • Critical facility monitoring system

ELECTRICAL 8/9 FLOOR

  • Backup generator power: 1,500 kW (N+1)
  • Fuel supply: 15,500 gallons
  • UPS system: 275 kVA (2N)
  • DC Power: 5,000 amps (2N)

SECURITY & COMPLIANCE

  • Key card access throughout the entire facility
  • Video surveillance: entrance cameras and cameras in all common areas on all floors
  • 24/7 access to authorized customer personnel via access lits
  • MMR access: two perimeters

BASE BUILDING

  • Diverse utility feeds at 208V post transformer
  • Utility power: 3,700 kW